HLS Series - High TDS Brackish Water RO 1,400 to 6,600 GPD
Commercial Reverse Osmosis Water Treatment for High TDS Brackish Water up to 15,000 PPM
- 1,400 to 6,600 Gallons/Day Reverse Osmosis Systems
- For Feed Water TDS up to 15,000 PPM
Designed to produce low dissolved solids water from high TDS brackish well water or similar source water, these RO systems use high efficiency reverse osmosis membranes in FRP membrane housings. The product water is used in applications such as water stores, whole house, ice makers, humidification, misting and a wide variety of other applications.
HLS Series RO systems incorporate careful design steps taken to minimize the highly corrosive nature of these brackish waters. All high pressure lines and components are made of corrosion resistant materials. These BWRO systems operate at pressures between 350 and 500 psi.
These reverse osmosis systems use the proven, reliable components and are mounted on a sturdy powder-coated metal frame. There are numerous design details learned from years of experience that are incorporated in our water filtration systems. Our process and fluid design ensures an optimum membrane life and minimizes the membrane fouling.
Request A Quote »Benefits
HLS Series Commercial RO Brackish Water System Benefits
- Compact, economical solution for high TDS brackish feed water
- Over 40 years of experience is reflected in our quality
- Heavy Duty, Powder Coated Frame
- Proven components used throughout the system
- Conservatively engineered for reliable long term performance
- Factory tested to ensure trouble-free operation
Details
HLS Series Commercial RO Brackish Water System Product Line
RO System Model No. |
RO System |
RO Membrane |
Line Sizes |
RO System |
Approx. Shipping Weight |
||||||
GPD |
m³/day |
Qty. |
Size |
Inlet |
Perm. |
Conc. |
Length |
Depth |
Height |
||
HLS-14A-116 |
1,400 |
5.3 |
1 |
4 × 40 |
1 |
½ |
½ |
20/51 |
24/61 |
55/140 |
400/181 |
HLS-24A-116 |
3,500 |
13.2 |
2 |
4 × 40 |
1 |
½ |
½ |
20/51 |
24/61 |
55/140 |
425/193 |
HLS-34A-216 |
4,600 |
17.4 |
3 |
4 × 40 |
1 |
½ |
½ |
20/51 |
32/82 |
55/140 |
450/204 |
HLS-44A-216 |
5,500 |
21 |
4 |
4 × 40 |
1 |
¾ |
¾ |
20/51 |
32/82 |
55/140 |
475/216 |
HLS-54A-216 |
6,200 |
23.5 |
5 |
4 × 40 |
1 |
¾ |
¾ |
20/51 |
32/82 |
55/140 |
500/227 |
HLS-64A-216 |
6,630 |
25 |
6 |
4 × 40 |
1 |
¾ |
¾ |
20/51 |
32/82 |
55/140 |
525/238 |
Notes and Voltage/ Ordering Information
- All dimensions and weights are approximate.
- Capacity Basis: 24 hrs/day
- Systems rated at: 77°F (25°C) using 15,000 ppm sodium chloride solution operating at approx. 350-500 psi pressure.
- Minimum feed pressure to RO System: 40-60 PSI. System capacity changes significantly with water temperature
- Chlorine must be removed with a carbon filter prior to the RO system, if present in feed water.
- Pretreatment for water hardness using a softener or antiscalant injection should be added to avoid scaling the membranes.
- Feed water turbidity: Less than 1 NTU; Feed water silt density index (SDI): 3 maximum. If exceeded, pretreatment with media filter recommended. All pretreatment equipment and SDI test kits are available from Applied Membranes.
- Voltage: Please add our voltage codes to the end of the model number when ordering.
Example: HLS-14A-216 = 220/230v, 1 ph, 60 hz.
|
|
|
Recommended Pre-Treatment Equipment (Sold Separately) |
|||
|
|
|
|
Features
Standard Equipment for HLS Series Commercial RO Brackish Water Systems
|
|
Microprocessor Controller for Automatic Operation
Monitors and/or Controls:
Controller Features:
|
UL508A LabeledI-ROC150S
LED Display:
|
Applications
Common Applications for HLS Series Commercial RO Brackish Water Systems
|
Parts
Optional Add-On Parts and Equipment for Commercial RO Systems
AMI's HLS Series High TDS RO Systems are available with a wide variety of optional add-on equipment. All assemblies include hardware and mounting equipment for easy upgrade to your new or existing system installation.
Wall Mount Filter Cartridges
Includes mounting bracket and Isolation Valves to close the line when changing the filter cartridge.
Part # A711
Filter cartridge must be ordered separately - common options are shown below. Any 20" Big Blue size cartridge can be installed. Click here to view our complete filter cartridge product selection.
Softeners & Media Filtration Pre/Post Treatment
AMI Media filters feature fully automatic backwash or regeneration for easy, trouble free maintenance. Ensure superior system operation and extended membrane life by providing proper pretreatment to the incoming feed water on a continuous basis. Common pretreatment or post-treatment methods include:
- Single or Twin Water Softener to remove hardness and scale.
- Multi-Media Filter for sediment filtration to approximately 10 microns.
- Carbon Filter to remove chlorine.
- Calcite Filter to neutralize the pH of the RO product water.
Click Here to visit the Media Filtration section of our site for detailed information on the full line of media filtration products we carry.
Chemical Injection System
Antiscalant injection as an alternative to a water softener for scale control, or
Sodium Metabisulfite injection as an alternative to a carbon filter to remove chlorine.
Water Quality Monitors
Pre-packaged wall-mountable water quality monitoring controls allow you to monitor the quality of the incoming feed or RO product water. Assembly includes the monitor, enclosure and sensor.
Available Options for Monitoring Incoming Feed Water Quality:
- ORP - 60Hz Part # A246, 50Hz Part # A247
- pH - 60Hz Part # A244, 50Hz Part # A245
Available Options for Monitoring RO Product Water Quality:
- Total Dissolved Solids (TDS) - 60Hz Part # A242, 50Hz Part # A243
- Resistivity - 60Hz Part # A248, 50Hz Part # A249
- pH - 60Hz Part # A244, 50Hz Part # A245
Ultraviolet (UV) Systems
Add an ultraviolet water sterilizer for a 99.9% reduction of bacteria and viruses in the feed and/or permeate line.
Note: For feed line, wall-mount filter cartridge assembly shown above is required.
Tank Pressure Controls
To automatically turn the RO system on or off with the permeate storage tank level. For use with a pressurized storage tank (sold separately).
- 220v/60Hz - Part # A621
Pressurized Storage Tank
Pressurized permeate storage tank available in 40 or 80 gallon volume. Assembly includes tank, valve, piping, tubing, and pressure gauge.
- 40 Gallon Tank Assembly - Part # A612-40
- 80 Gallon Tank Assembly - Part # A612-80
Tank Level Controls
Turns system on or off according to the water level in an atmospheric storage tank.
- Dual float assembly provides system on/off controls.
Part # YFL2PPAS - Triple float assembly provides system on/off as well as low level protection on/off for a repressurization pump.
Part # YFL3PPAS
Atmospheric storage tank and repressurization pump are sold separately.
Atmospheric Storage Tank
Atmospheric Permeate Storage tank. Assembly includes bulkheads and vent filter. For use with Tank Level Controls (sold separately).
- 200 Gallon Part # A613-200
- 400 Gallon Part # A613-500
Delivery System
20 GPM, 50 PSI, 220v/1ph/50-60Hz
Includes Pump, 40 Gallon Pressure Tank, Controls and Fittings
Part # A606-216
Prefilter Pressure Gauge
To allow for monitoring of the in and out pressure of the prefilter in order to indicate when the cartridge needs to be changed. Assembly includes pressure gauge and fittings.
Part # A623
Floor Casters Kit
2 Locking casters and 2 Swivel casters to mount at the base of the stand for ease of system mobility.
Part #: A625
Replacement Parts & Consumables for HLS Series Brackish Water Reverse Osmosis Systems
- Replacement Reverse Osmosis Membranes for Commercial RO Systems
- Replacement Membrane Pressure Vessels for Commercial RO Systems
- Replacement Sediment Filters for Commercial RO Systems
- Replacement Carbon Filters for Commercial RO Systems
- Replacement Filter Housings for Commercial RO Systems
- Replacement Components for Commercial RO Systems
- Membrane Cleaning Cartridges for Commercial RO Systems
Contact us
for a quote or for any additional information
or call us at 1.800.321.9321